In article , hackus wrote:
>hello all. i have a single zone hot water heating system with an
>external coil. the circulator is continuously run for domestic hot
>water. the problem started with gurgling sounds from the baseboard
>radiators. it sounded as if air may have gotten into the system.
Yep.
[paraphrasing remainder: Bled system, noise went away, noise came back, bled
system, noise went away, noise came back, repeat...]
You have a leak somewhere -- possibly in that expansion tank. If it's a
bladder-type tank, there may be a hole in the bladder. Air can also enter the
system through leaks in the bleeder valves at the baseboard radiators, so
check those to make sure that they're closed tightly and not leaking.
--